1. The following measurements were obtained from tests: carried out on a 10-kVA, 2300:230-V, 60-Hz distribution transformer: -Open-circuit test, with the low-potential winding excited: Applied potential difference, Voc = 230 V Current, Ioc 0.45 A = Input power, Poc = 70 W -Short-circuit test, with the high-potential winding excited: Applied potential difference, Vsc =120 V Current, Isc 4.5 A = Input power, Psc = 240 W Winding resistances, measured by dc bridge: = Rhp 5.80 2, R1p = 0.0605 2 (a) Determine the equivalent circuit of the transformer referred to the low- potential side.

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter3: Power Transformers
Section: Chapter Questions
Problem 3.28MCQ
icon
Related questions
Question
Please do not copy chegg solutions
(b) Express the exciting current of the transformer as a
rated full-load current.
percentage of the
Transcribed Image Text:(b) Express the exciting current of the transformer as a rated full-load current. percentage of the
1. The following measurements were obtained from tests: carried out on
a 10-kVA, 2300:230-V, 60-Hz distribution transformer:
-Open-circuit test, with the low-potential winding excited:
Applied potential difference, Voc = 230 V
Current, Ioc 0.45 A
=
Input power, Poc = 70 W
-Short-circuit test, with the high-potential winding excited:
Applied potential difference, Vsc =120 V
Current, Isc 4.5 A
=
Input power, Psc
= 240 W
Winding resistances, measured by dc bridge:
=
Rhp 5.80 2, R1p = 0.0605
(a) Determine the equivalent circuit of the transformer referred to the low-
potential side.
Transcribed Image Text:1. The following measurements were obtained from tests: carried out on a 10-kVA, 2300:230-V, 60-Hz distribution transformer: -Open-circuit test, with the low-potential winding excited: Applied potential difference, Voc = 230 V Current, Ioc 0.45 A = Input power, Poc = 70 W -Short-circuit test, with the high-potential winding excited: Applied potential difference, Vsc =120 V Current, Isc 4.5 A = Input power, Psc = 240 W Winding resistances, measured by dc bridge: = Rhp 5.80 2, R1p = 0.0605 (a) Determine the equivalent circuit of the transformer referred to the low- potential side.
Expert Solution
steps

Step by step

Solved in 7 steps with 6 images

Blurred answer
Knowledge Booster
Three Phase Transformer
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning