A:- A commercial refrigerator with refrigerant-134a as shown in Fig. Q3A as the working fluid is used to keep the refrigerated space at -35 °C by rejecting waste heat to cooling water that enters the condenser at 18 °C at a rate of 0.25 kg/s and leaves at 26 °C. The refrigerante enters the condenser at 1.2 MPa and 50 °C and leaves at the same pressure subcooled by 5 °C. If the compressor consumes 3.3 kW of power, determine (a) the mass flow rate of the refrigerant, (b) the refrigeration load, and (c) the COP. 1:2 MPa 5°C subcooled Expansion valve Fig. Q3A Condenser Evaporator Water 18% 1.2 MP 50PC Compressor

Refrigeration and Air Conditioning Technology (MindTap Course List)
8th Edition
ISBN:9781305578296
Author:John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Publisher:John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Chapter45: Domestic Refrigerators And Freezers
Section: Chapter Questions
Problem 12RQ: Refrigerators currently being manufactured in the United States are using______as their refrigerant.
icon
Related questions
Question
A:-
A commercial refrigerator with refrigerant-134a as
shown in Fig. Q3A as the working fluid is used to keep
the refrigerated space at -35 °C by rejecting waste heat
to cooling water that enters the condenser at 18 °C at a
rate of 0.25 kg/s and leaves at 26 °C. The refrigerante
enters the condenser at 1.2 MPa and 50 °C and leaves
at the same pressure subcooled by 5 °C. If the
compressor consumes 3.3 kW of power, determine (a)
the mass flow rate of the refrigerant, (b) the
refrigeration load, and (c) the COP.
12 MPa
5°C subcooled
Expansion
valve
Fig. Q3A
Condenser
Evaporator
Qu
Water
18%
1.2 MP
56PC
Compressor
Transcribed Image Text:A:- A commercial refrigerator with refrigerant-134a as shown in Fig. Q3A as the working fluid is used to keep the refrigerated space at -35 °C by rejecting waste heat to cooling water that enters the condenser at 18 °C at a rate of 0.25 kg/s and leaves at 26 °C. The refrigerante enters the condenser at 1.2 MPa and 50 °C and leaves at the same pressure subcooled by 5 °C. If the compressor consumes 3.3 kW of power, determine (a) the mass flow rate of the refrigerant, (b) the refrigeration load, and (c) the COP. 12 MPa 5°C subcooled Expansion valve Fig. Q3A Condenser Evaporator Qu Water 18% 1.2 MP 56PC Compressor
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 3 steps with 3 images

Blurred answer
Knowledge Booster
Refrigeration and Air Conditioning
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, mechanical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Refrigeration and Air Conditioning Technology (Mi…
Refrigeration and Air Conditioning Technology (Mi…
Mechanical Engineering
ISBN:
9781305578296
Author:
John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Publisher:
Cengage Learning