(a) the full load efficiency at unity power factor;

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter3: Power Transformers
Section: Chapter Questions
Problem 3.9P
icon
Related questions
Question
Calculate (a) the full load efficiency at unity power factor; (b) the voltage at the secondary
terminals when supplying full load secondary current at power factor (1) unity (2) 0.8
lagging (3) 0.8 leading, for the 4kVA, 200/400V, 50Hz, single phase transformer, of
which the following are the test figures: Open-circuit with 200V applied to primary
winding: current 0.8A, power 70W. Short-circuit with 17.5V applied to secondary (high
voltage) side: current 9A, power 50W.
Transcribed Image Text:Calculate (a) the full load efficiency at unity power factor; (b) the voltage at the secondary terminals when supplying full load secondary current at power factor (1) unity (2) 0.8 lagging (3) 0.8 leading, for the 4kVA, 200/400V, 50Hz, single phase transformer, of which the following are the test figures: Open-circuit with 200V applied to primary winding: current 0.8A, power 70W. Short-circuit with 17.5V applied to secondary (high voltage) side: current 9A, power 50W.
Expert Solution
steps

Step by step

Solved in 3 steps with 3 images

Blurred answer
Knowledge Booster
Compensation Techniques in Transmission Line
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning