An 11 kV generating station has four identical 3-phase alternators Gl, G2, G3 and G4 each of L0 MVA capacity and l2%o reaclarce. There are two section of bus-bar P and Q, linked by a reactor X rated at 10 MVA with 24o/oreactance. From section Q load is taken through a 6 MVA, i 1kV/66kV step-up transformer (T1) having a reactance of 37o. Determine the fault current if a three-phase short-circuit occurs near the high voltage terminal of the transformer (F) as shown in Figure. Assume prefault voltages to be 1 pu and prefault currents to be zero

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter2: Fundamentals
Section: Chapter Questions
Problem 2.16P: A single-phase, 120V(rms),60Hz source supplies power to a series R-L circuit consisting of R=10 and...
icon
Related questions
Question

An 11 kV generating station has four identical 3-phase alternators
Gl, G2, G3 and G4 each of L0 MVA capacity and l2%o reaclarce.
There are two section of bus-bar P and Q, linked by a reactor X rated
at 10 MVA with 24o/oreactance. From section Q load is taken through
a 6 MVA, i 1kV/66kV step-up transformer (T1) having a reactance of
37o. Determine the fault current if a three-phase short-circuit occurs
near the high voltage terminal of the transformer (F) as shown in
Figure.
Assume prefault voltages to be 1 pu and prefault currents to be zero

G1
G2
G3
G4
11 kV
11 kV
P
Q
T1
Figure-3
An 11 kV generating station has four identical 3-phase alternators
G1, G2, G3 and G4 each of 10 MVA capacity and 12% reactance.
There are two section of bus-bar P and Q, linked by a reactor X rated
at 10 MVA with 24% reactance. From section Q load is taken through
a 6 MVA, 11kV/66KV step-up transformer (T1) having a reactance of
3%. Determine the fault current if a three-phase short-circuit occurs
near the high voltage terminal of the transformer (F) as shown in
Figure-3.
Assume prefault voltages to be 1 pu and prefault currents to be zero.
Transcribed Image Text:G1 G2 G3 G4 11 kV 11 kV P Q T1 Figure-3 An 11 kV generating station has four identical 3-phase alternators G1, G2, G3 and G4 each of 10 MVA capacity and 12% reactance. There are two section of bus-bar P and Q, linked by a reactor X rated at 10 MVA with 24% reactance. From section Q load is taken through a 6 MVA, 11kV/66KV step-up transformer (T1) having a reactance of 3%. Determine the fault current if a three-phase short-circuit occurs near the high voltage terminal of the transformer (F) as shown in Figure-3. Assume prefault voltages to be 1 pu and prefault currents to be zero.
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 2 steps with 1 images

Blurred answer
Knowledge Booster
Three Phase Transformer
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning