A power system comprises of a steam-turbine generator feeding a 161kV transmission line through a 15kV/161kV step-up transformer rated 80 MVA with a reactance of 10%. The transmission having a reactance of 100 Ω feeds a 161kV/33kV 100 MVA step-down transformer with a reactance of 12.5%. 50 MW of power is fed to a load on the secondary side of the step-down transformer at 25kV and power factor of 0.9 lagging. Use the given information to answer the following sub-questions: a) Draw a single line diagram to depict the power system [AN4] b) Convert your single line diagram into a reactance diagram [AN4] c) Determine the per unit load current [AN4]

Delmar's Standard Textbook Of Electricity
7th Edition
ISBN:9781337900348
Author:Stephen L. Herman
Publisher:Stephen L. Herman
Chapter28: Three-phase Transformers
Section: Chapter Questions
Problem 2PA
icon
Related questions
icon
Concept explainers
Question

A power system comprises of a steam-turbine generator feeding a 161kV transmission line through a 15kV/161kV step-up transformer rated 80 MVA with a reactance of 10%. The transmission having a reactance of 100 Ω feeds a 161kV/33kV 100 MVA step-down transformer with a reactance of 12.5%. 50 MW of power is fed to a load on the secondary side of the step-down transformer at 25kV and power factor of 0.9 lagging. Use the given information to answer the following sub-questions:
a) Draw a single line diagram to depict the power system [AN4]
b) Convert your single line diagram into a reactance diagram [AN4]
c) Determine the per unit load current [AN4]
d) Calculate the per unit voltage drop on the transmission line [AN10]
e) Calculate also the sending end voltage [AN3]
Use an overall base of 100 MVA.
[

Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 3 steps with 3 images

Blurred answer
Follow-up Questions
Read through expert solutions to related follow-up questions below.
Follow-up Question

A power system comprises of a steam-turbine generator feeding a 161kV transmission line through a 15kV/161kV step-up transformer rated 80 MVA with a reactance of 10%. The transmission having a reactance of 100 Ω feeds a 161kV/33kV 100 MVA step-down transformer with a reactance of 12.5%. 50 MW of power is fed to a load on the secondary side of the step-down transformer at 25kV and power factor of 0.9 lagging. Use the given information to answer the following sub-questions:
d) Calculate the per unit voltage drop on the transmission line 
e) Calculate also the sending end voltage 
Use an overall base of 100 MVA.

Solution
Bartleby Expert
SEE SOLUTION
Follow-up Question

d) Calculate the per unit voltage drop on the transmission line 
e) Calculate also the sending end voltage 
Use an overall base of 100 MVA.

Solution
Bartleby Expert
SEE SOLUTION
Knowledge Booster
Load flow analysis
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Delmar's Standard Textbook Of Electricity
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning