Example 11.2 A 60-Hz synchronous generator having inertia constant H = 9.94 MJ/MVA and a transient reactance X = 0.3 per unit is connected to an infinite bus through a purely reactive circuit as shown in Figure 11.7. Reactances are marked on the diagram on a common system base. The generator is delivering real power of 0.6 per unit, 0.8 power factor lagging to the infinite bus at a voltage of V = 1 per unit. 2 X₁ = 0.2 X12 = 0.3 x = 0.3 FIGURE 11.7 X12=0.3 v = 1.0 ∞ A three phase fault occurs at the middle of one lines, the fault is cleared, and the faulted line is isolated. Determine the power angle equation for the prefault, during, and postfault.

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter12: Power System Controls
Section: Chapter Questions
Problem 12.9P
icon
Related questions
Question
Example 11.2
A 60-Hz synchronous generator having inertia constant H = 9.94 MJ/MVA and
a transient reactance X = 0.3 per unit is connected to an infinite bus through
a purely reactive circuit as shown in Figure 11.7. Reactances are marked on the
diagram on a common system base. The generator is delivering real power of 0.6
per unit, 0.8 power factor lagging to the infinite bus at a voltage of V = 1 per unit.
2
X₁ = 0.2
X12 = 0.3
x = 0.3
FIGURE 11.7
X12=0.3
v = 1.0
∞
A three phase fault occurs at the middle of one lines, the fault is cleared, and the faulted
line is isolated. Determine the power angle equation for the prefault, during, and postfault.
Transcribed Image Text:Example 11.2 A 60-Hz synchronous generator having inertia constant H = 9.94 MJ/MVA and a transient reactance X = 0.3 per unit is connected to an infinite bus through a purely reactive circuit as shown in Figure 11.7. Reactances are marked on the diagram on a common system base. The generator is delivering real power of 0.6 per unit, 0.8 power factor lagging to the infinite bus at a voltage of V = 1 per unit. 2 X₁ = 0.2 X12 = 0.3 x = 0.3 FIGURE 11.7 X12=0.3 v = 1.0 ∞ A three phase fault occurs at the middle of one lines, the fault is cleared, and the faulted line is isolated. Determine the power angle equation for the prefault, during, and postfault.
Expert Solution
steps

Step by step

Solved in 2 steps

Blurred answer
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning