EBK ELECTRICAL WIRING RESIDENTIAL
EBK ELECTRICAL WIRING RESIDENTIAL
19th Edition
ISBN: 9781337516549
Author: Simmons
Publisher: CENGAGE LEARNING - CONSIGNMENT
bartleby

Concept explainers

bartleby

Videos

Textbook Question
Book Icon
Chapter 18, Problem 18R

List the proper trade size of electrical metallic tubing for the following. Assume that THHN insulated conductors are used. See Chapter 9, Table C1, NEC.

  1. a. Three 14 AWG ___________________
  2. b. Four 14 AWG ___________________
  3. c. Five 14 AWG ___________________
  4. d. Six 14 AWG ___________________
  5. e. Three 12 AWG ___________________
  6. f. Four 12 AWG ___________________
  7. g. Five 12 AWG ___________________
  8. h. Six 12 AWG ___________________
  9. i. Six 10 AWG ___________________
  10. j. Four 8 AWG ___________________

(a)

Expert Solution
Check Mark
To determine

Find the trade size EMT that is required for three 14 AWG THHN conductors.

Answer to Problem 18R

The trade size 12 EMT is required for three 14 AWG THHN conductors.

Explanation of Solution

Discussion:

Refer to Table C1, Annex C of the NEC shows that three 14 AWG THHN conductors require trade size 12 EMT. EMT is permitted to serve as the equipment ground as provided in NEC 250.118(4).

Conclusion:

Thus, the trade size 12 EMT is required for three 14 AWG THHN conductors.

(b)

Expert Solution
Check Mark
To determine

Find the trade size EMT that is required for four 14 AWG THHN conductors.

Answer to Problem 18R

The trade size 12 EMT is required for four 14 AWG THHN conductors.

Explanation of Solution

Discussion:

Refer to Table C1, Annex C of the NEC shows that four 14 AWG THHN conductors require trade size 12 EMT. The EMT is permitted to serve as the equipment ground as provided in NEC 250.118(4).

Conclusion:

Thus, the trade size 12 EMT is required for four 14 AWG THHN conductors.

(c)

Expert Solution
Check Mark
To determine

Find the trade size EMT that is required for five 14 AWG THHN conductors.

Answer to Problem 18R

The trade size 12 EMT is required for five 14 AWG THHN conductors.

Explanation of Solution

Discussion:

Refer to Table C1, Annex C of the NEC shows that five 14 AWG THHN conductors require trade size 12 EMT. EMT is permitted to serve as the equipment ground as provided in NEC 250.118(4).

Conclusion:

Thus, the trade size 12 EMT is required for five 14 AWG THHN conductors.

(d)

Expert Solution
Check Mark
To determine

Find the trade size EMT is required for six 14 AWG THHN conductors.

Answer to Problem 18R

The trade size 12 EMT is required for six 14 AWG THHN conductors.

Explanation of Solution

Discussion:

Refer to Table C1, Annex C of the NEC shows that six 14 AWG THHN conductors require trade size 12 EMT. EMT is permitted to serve as the equipment ground as provided in NEC 250.118(4).

Conclusion:

Thus, the trade size 12 EMT is required for six 14 AWG THHN conductors.

(e)

Expert Solution
Check Mark
To determine

Find the trade size EMT is required for three 12 AWG THHN conductors.

Answer to Problem 18R

The trade size 12 EMT is required for three 12 AWG THHN conductors.

Explanation of Solution

Discussion:

Refer to Table C1, Annex C of the NEC shows that three 12 AWG THHN conductors require trade size 12 EMT. EMT is permitted to serve as the equipment ground as provided in NEC 250.118(4).

Conclusion:

Thus, the trade size 12 EMT is required for three 12 AWG THHN conductors.

(f)

Expert Solution
Check Mark
To determine

Find the trade size EMT that is required for four 12 AWG THHN conductors.

Answer to Problem 18R

The trade size 12 EMT is required for four 12 AWG THHN conductors.

Explanation of Solution

Discussion:

Refer to Table C1, Annex C of the NEC shows that four 12 AWG THHN conductors require trade size 12 EMT. EMT is permitted to serve as the equipment ground as provided in NEC 250.118(4).

Conclusion:

Thus, the trade size 12 EMT is required for four 12 AWG THHN conductors.

(g)

Expert Solution
Check Mark
To determine

Find the trade size EMT that is required for five 12 AWG THHN conductors.

Answer to Problem 18R

The trade size 12 EMT is required for five 12 AWG THHN conductors.

Explanation of Solution

Discussion:

Refer to Table C1, Annex C of the NEC shows that five 12 AWG THHN conductors require trade size 12 EMT. EMT is permitted to serve as the equipment ground as provided in NEC 250.118(4).

Conclusion:

Thus, the trade size 12 EMT is required for five 12 AWG THHN conductors.

(h)

Expert Solution
Check Mark
To determine

Find the trade size EMT that is required for six 12 AWG THHN conductors.

Answer to Problem 18R

The trade size 34 EMT is required for six 12 AWG THHN conductors.

Explanation of Solution

Discussion:

Refer to Table C1, Annex C of the NEC shows that six 12 AWG THHN conductors require trade size 34 EMT. EMT is permitted to serve as the equipment ground as provided in NEC 250.118(4).

Conclusion:

Thus, the trade size 34 EMT is required for six 12 AWG THHN conductors.

(i)

Expert Solution
Check Mark
To determine

Find the trade size EMT that is required for six 10 AWG THHN conductors.

Answer to Problem 18R

The trade size 12 EMT is required for six 10 AWG THHN conductors.

Explanation of Solution

Discussion:

Refer to Table C1, Annex C of the NEC shows that six 10 AWG THHN conductors require trade size 12 EMT. EMT is permitted to serve as the equipment ground as provided in NEC 250.118(4).

Conclusion:

Thus, the trade size 12 EMT is required for six 10 AWG THHN conductors.

(j)

Expert Solution
Check Mark
To determine

Find the trade size EMT that is required for four 8 AWG THHN conductors.

Answer to Problem 18R

The trade size 34 EMT is required for four 8 AWG THHN conductors.

Explanation of Solution

Discussion:

Refer to Table C1, Annex C of the NEC shows that four 8 AWG THHN conductors require trade size 34 EMT. EMT is permitted to serve as the equipment ground as provided in NEC 250.118(4).

Conclusion:

Thus, the trade size 34 EMT is required for four 8 AWG THHN conductors.

Want to see more full solutions like this?

Subscribe now to access step-by-step solutions to millions of textbook problems written by subject matter experts!
Students have asked these similar questions
1. A14/2 type copper used for a general lighting branch circuit.                                                Ampacity:______________              Maximum Fuse or Circuit Breakers Sizes:________________      2.Three 8 AWG copper conductors with THHN insulation Installed in garage in electrical metallic tubing (EMT). The ambient temperature in the garage can reach as high as 110'F. All termination points for this circuit are rated 60'C.                            Ampacity:______________                  Maximum Fuse or Circuit Breakers Sizes:________________ 3.Four 4 AWG copper conductor with THWN insulation imstalled in EMT in a basement. All termination points are rated at 60'C.                                 Ampacity:______________                  Maximum Fuse or Circuit Breakers Sizes:________________  4. An 8/3 Type UF copper cable installed underground from a house to a detached garage to feed a 120/240-volt subpanel. All termination points are rated at 60'C.…
14: In a natural circulation solar water heater, collector has a glass cover on the top and an ________________ material at the bottom. a. Insulating b. Sheets c. Steel d. Tubes 15: text ____________ wind mill consists of narrow rims and wire spokes. a. Single bladed b. Vertical Axis c. Double bladed d. Multibladed
7.A. Ferrous metal raceways or enclosures are made with _______ content.A. steel or brassB. aluminum or ironC. brass or aluminumD. iron or steel7.B. The size of a grounding electrode conductor for a service or separately derived system is generally basedon the size of the largestA. ungrounded supply conductor.B. equipment grounding conductor.C. grounded electrode.D. bonding jumper.7.C. Which of the following statements about bonding is true?A. The joint or termination must offer opposition in the circuit for effective electrical connections.B. Effective bonding keeps impedance high if a fault should occur.C. The entire electrical safety circuit is only as good as its strongest bonded link.D. Bonding connections must endure high levels of fault current until overcurrent protective devices can operate.
Knowledge Booster
Background pattern image
Electrical Engineering
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
SEE MORE QUESTIONS