A 120-volt branch circuit supplies a resistive heating load of 10 amperes. The distance from the panel to the heater is approximately 140 ft. Calculate the voltage drop using (a) 14 AWG, (b) 12 AWG, (c) 10 AWG, (d) 8 AWG copper conductors. See 210.19(A), Informational Note No. 4 and 215.2(A)(1), Informational Note No. 2.
(a)
Find the value of voltage drop in 14 AWG copper wire.
Answer to Problem 35R
The obtained value of voltage drop in 14 AWG copper wire is
Explanation of Solution
Given data:
Supply voltage is 120-volt.
Current is 10 A.
The distance between panel and heater is approximately 140 ft.
14 AWG copper conductor.
Calculation:
Write the expression for voltage drop in single-phase circuit.
Here,
K is the approximate resistance in ohms per circular-mil foot at
I is the current, and
CMA is cross-sectional area of the conductors.
Modify Equation (1) for 14 AWG copper wire.
Refer TABLE 4-7 in the textbook for circular mil area (CMA) for many of the common conductors.
The value of CMA for 14 AWG is 4110.
Substitute
Conclusion:
Thus, the obtained value of the voltage drop for 14 AWG copper wire is
(b)
Find the value of voltage drop in 12 AWG copper wire.
Answer to Problem 35R
The obtained value of the voltage drop for 12 AWG copper wire is
Explanation of Solution
Given data:
12 AWG copper conductor.
Calculation:
Modify Equation (1) for 12 AWG copper wire.
Refer TABLE 4-7 in the textbook for circular mil area (CMA) for many of the common conductors.
The value of CMA for 12 AWG is 6530.
Substitute
Conclusion:
Thus, the obtained value of voltage drop for 12 AWG copper wire is
(c)
Find the value of voltage drop in 10 AWG copper wire.
Answer to Problem 35R
The obtained value of voltage drop for 10 AWG copper wire is
Explanation of Solution
Given data:
10 AWG copper conductor.
Calculation:
Modify Equation (1) for 10 AWG copper wire.
Refer TABLE 4-7 in the textbook for circular mil area (CMA) for many of the common conductors.
The value of CMA for 10 AWG is 10,380.
Substitute
Conclusion:
Thus, the obtained value of voltage drop for 10 AWG copper wire is
(d)
Find the value of the voltage drop in 8 AWG copper wire.
Answer to Problem 35R
The obtained value of the voltage drop for 8 AWG copper wire is
Explanation of Solution
Given data:
8 AWG copper conductor.
Calculation:
Modify Equation (1) for 8 AWG copper wire.
Refer TABLE 4-7 in the textbook for circular mil area (CMA) for many of the common conductors.
The value of CMA for 8 AWG is 16,510.
Substitute
Conclusion:
Thus, the obtained value of the voltage drop for 8 AWG copper wire is
Want to see more full solutions like this?
Chapter 4 Solutions
EBK ELECTRICAL WIRING RESIDENTIAL
Additional Engineering Textbook Solutions
Introductory Circuit Analysis (13th Edition)
Electric Circuits (10th Edition)
Principles and Applications of Electrical Engineering
Electric Circuits. (11th Edition)
Engineering Electromagnetics
Principles Of Electric Circuits
- A. Discuss the arcing phenomenon in a circuit breaker. B. Discuss the types of oil circuit breakers. With referencesarrow_forwardQUESTION 5 We would like to run the power wires for both cooling pumps in the same RMC from the Breaker panel to a junction box above the control panel. What size ungrounded conductors do we need for the 100 amp load? All conductors have typeTHHN insulation. A #6 AWG B #3 AWG C #4 AWG D #1 AWGarrow_forward3. The zero sequence current is times the current in neutral wire.arrow_forward
- 70. A circuit supplies a continuous load of 38 amperes and is protected by a 50-amperecircuit breaker. All conductor terminations in the circuit are rated at 75°C. If the circuit conductors are THWN copper, determine the minimum size permitted for the circuit. A. 60 A B. 50 A C. 40 A D. 70 Aarrow_forwardWe are running 3 wires and a ground in a RMC to a control panel with a 60 amp circuit breaker disconnect in the control panel. The conduit is run along the ceiling where the ambient air temperature is 100 degrees. The control panel feeds our secondary cooling pump. What size are the ungrounded conductors? All conductors have typeTHHN insulation. A #6 AWG B 600 Kcmil C #8 AWG D #2 AWG What size RMC do we need? A 3" B 3/4" C 1" D 1 1/2"arrow_forwardDiscuss the types of oil circuit breakers. Please write more answerarrow_forward
- Ohm's Law states that the electric current flowing though a ________ is directly proportional to the ________. Select one: a. closed circuit --- total resistance b. closed circuit --- switch resistance c. open circuit --- supply voltage d. closed circuit --- supply voltagearrow_forwardIdentify the installation symbol O Two way One gang switch O Two way Two gang switch O One way Two gang switch O One way One gang switcharrow_forward12 - Due to the effect of the resistance of the cable connected to RTD, two-wire cables up to ……. meters and three-wire cables up to ……... meters are used in standard designs. A) 10-150B) 40-500C) 50-195D) 30-230E) 200-1000arrow_forward
- Please kindly help me to answer this question. Please provide all the solutions, givens, and formulas used. Thank you very much! The exciting current of an electromagnet is rated at 12 amperes. When connected across a 122 - volt source the current is 14 amperes. Determine the ohms in a resistor which must be connected in series to limit the current to (a) rated value, and (b) 9 amperes.arrow_forward3. A 2-wire d.c. distributor AB 500 metres long is fed from point .4 and is loaded as under: Distance from feeding point.4 (in metres) Load (amperes) If the specific resistance of copper is 1-7x 10 Sm what must be the cross-section of each wire in order that the voltage drop in the dismbutor shall not exceed 10 volts ? 100 300 400 500 20 40 40 50 [1 734 cm]arrow_forwardIf the cable in Figure ran for the whole of its length, grouped with others of the same size in a high ambient temperature, and was totally surrounded with thermal insulation, The correction factors considered will be----------- Fuseboard High ambient temperature Cable Grouping of cables Thermal insulation Load BS 3036 fuse O a. Cg O b. All Ca,Cg.Ci and Cf O c. Ci O d. Caarrow_forward
- EBK ELECTRICAL WIRING RESIDENTIALElectrical EngineeringISBN:9781337516549Author:SimmonsPublisher:CENGAGE LEARNING - CONSIGNMENT