A balanced inductive load is connected to a 550 V, 60 Hz, three-phase supply. The line current is 20A and the total power delivered to the load is 10kW. It is desired to improve the power factor to 0.9 lagging. Find: a) The power factor before correction b)The line current after correction c)Find the kVAR and the capacitor in µF.

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter6: Power Flows
Section: Chapter Questions
Problem 6.61P
icon
Related questions
Question

Ple

A balanced inductive load is connected to a 550 V, 60 Hz, three-phase supply. The line
current is 20A and the total power delivered to the load is 10kW. It is desired to
improve the power factor to 0.9 lagging. Find:
a)The power factor before correction
b)The line current after correction
c)Find the kVAR and the capacitor in µF.
Transcribed Image Text:A balanced inductive load is connected to a 550 V, 60 Hz, three-phase supply. The line current is 20A and the total power delivered to the load is 10kW. It is desired to improve the power factor to 0.9 lagging. Find: a)The power factor before correction b)The line current after correction c)Find the kVAR and the capacitor in µF.
Expert Solution
steps

Step by step

Solved in 5 steps with 8 images

Blurred answer
Knowledge Booster
Y parameter
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning